Voltage Drop Calculator

Check the voltage drop on any run, find the smallest wire that works, or see how far you can go. Built for Canadian wiring, with the CEC 3% and 5% limits, and for 12 V and 24 V low-voltage work like maglocks, strikes and cameras.

What are you powering?

What do you want to know?
Power type
Wire material

Measure from the panel or power supply to the load, along the cable route. Don’t double it. The formula counts the return wire.

Advanced settings

Warmer wire has more resistance. Use 1.0 power factor for heaters, lights and electronics, and about 0.85 for motors. Steel conduit adds a little reactance on AC.

What each setting means

SettingWhat to enter
Power typeDC for batteries, solar and most lock power supplies. AC single-phase for 120 V, 240 V, 277 V and 347 V circuits and for 24 V AC camera transformers. AC 3-phase for 208 V and 600 V equipment and feeders.
VoltageThe supply voltage: the panel voltage, or the output of the power supply or transformer. For three-phase, use the line-to-line voltage (208 V, 480 V, 600 V).
LoadThe current the load actually draws, or its wattage. If you don’t know it, the CEC uses 80% of the breaker or fuse rating. Tap “Use 80% of the breaker” to fill it in.
One-way lengthThe cable route from the panel or supply to the load, not the straight line and not the round trip.
Wire sizeAWG or kcmil, with the metric area shown beside it. Switch to Wire size mode and the calculator picks the smallest size that passes.
Allowed drop3% for one feeder or branch circuit, 5% for the whole run from the service to the load, 10% for most 12 V and 24 V devices, or your own figure.
AdvancedConductor temperature, power factor, steel conduit and parallel conductors. The defaults suit most jobs.

What voltage drop is, and why it matters

Every wire has some resistance. When current flows through it, part of the voltage is used up pushing the current along the wire and turns into heat. The load at the far end gets less voltage than the panel or power supply puts out. That difference is the voltage drop.

A small drop is normal. A large one causes problems that are easy to blame on the equipment:

  • Motors run hotter, draw more current and wear out sooner.
  • LED fixtures and drivers flicker, dim or drop out at the end of a long run.
  • Maglocks lose holding force, and electric strikes fail to release.
  • Outdoor cameras reboot on cold nights when their heaters switch on and the current jumps.
  • The wire wastes power as heat, every hour the circuit is loaded.
Diagram of a 120 V circuit with 16 A over 25 m of 12 AWG copper: the panel supplies 120 V, the load receives 114.8 V, 5.17 V (4.31%) is lost in the hot and neutral wires and 83 W turns into heat
The panel puts out 120 V, but the wire uses some of it on the way. At 16 A over 25 m of 12 AWG copper, the load sees about 114.8 V.

The voltage drop formula

For DC and single-phase AC circuits:

Voltage drop (V) = 2 × I × L × R

For balanced three-phase circuits:

Voltage drop (V) = 1.732 × I × L × R

Then turn it into a percentage of the supply voltage:

Voltage drop (%) = Voltage drop ÷ Supply voltage × 100

I is the load current in amps, L is the one-way length in metres, and R is the resistance of one conductor in ohms per metre. The 2 on single-phase and DC circuits counts the wire out and the wire back. On three-phase the return currents cancel, and the line-to-line drop is √3 (1.732) times the drop in one conductor.

Resistance comes from the conductor’s cross-section and the metal it is made of:

R (Ω/m) = ρ ÷ A × [1 + α × (T − 20)]

Here ρ is 0.01724 Ω·mm²/m for copper and 0.02826 Ω·mm²/m for aluminum at 20 °C, A is the area in mm², α is 0.00393 for copper and 0.00403 for aluminum, and T is the conductor temperature in °C. The calculator adds 2% for stranding. If you work in feet and circular mils, the same formula is often written as VD = 2 × K × I × L ÷ CM, with K about 12.9 for copper and 21.2 for aluminum at 75 °C.

On AC loads with a power factor below 1, such as motors, the inductive reactance of the wire also counts. The calculator then uses the effective impedance from NEC Chapter 9, Table 9: Z = R × cos θ + X × sin θ. At a power factor of 1, Z is simply R.

Floor plan showing a maglock cable route from a power supply: 3 m up to the ceiling, 26 m along the corridor, 8 m across and 1 m down for a one-way length of 38 m, compared with a 24 m straight line
Measure the route the cable actually takes, one way. The formula doubles it for the return conductor, so don’t double it yourself.

Three worked examples

1. A 120 V circuit on a 20 A breaker, 25 m away

The load isn’t known, so the CEC method uses 80% of the breaker: 16 A. 12 AWG copper at 75 °C has a resistance of 6.46 Ω/km, or 0.00646 Ω/m.

2 × 16 A × 25 m × 0.00646 Ω/m = 5.17 V
5.17 V ÷ 120 V × 100 = 4.31%

That is over the 3% limit. 10 AWG (0.00407 Ω/m) brings it to 3.25 V, or 2.71%. The other option is to keep 12 AWG and shorten the run to about 17.4 m.

2. A 12 V DC maglock, 45 m from the power supply

The lock draws 0.5 A. The run uses 18 AWG copper, which is 0.0230 Ω/m at 40 °C.

2 × 0.5 A × 45 m × 0.0230 Ω/m = 1.04 V
1.04 V ÷ 12 V × 100 = 8.64%, so the lock sees 10.96 V

That is inside a 10% device tolerance, but with almost nothing to spare. 16 AWG cuts it to 0.65 V (5.44%). A better fix is to run the lock at 24 V: the current halves to 0.25 A, the same 18 AWG drops only 0.52 V, and that is 2.16% of 24 V. Doubling the voltage cut the percentage to a quarter.

3. A 600 V three-phase feeder, 100 A, 150 m in steel conduit

The load has a power factor of 0.9. For 3 AWG copper at 75 °C, R is 0.802 Ω/km and the reactance in steel conduit is 0.194 Ω/km.

Z = 0.802 × 0.9 + 0.194 × 0.436 = 0.806 Ω/km
1.732 × 100 A × 150 m × 0.000806 Ω/m = 20.9 V
20.9 V ÷ 600 V × 100 = 3.49%

Over 3%. 2 AWG copper brings it to 17.0 V, or 2.83%, and cuts the heat lost in the feeder from about 3.6 kW to 2.9 kW at full load.

Voltage drop limits in Canada: CEC Rule 8-102

In Canada, voltage drop is a code requirement, not a suggestion. Rule 8-102 of the Canadian Electrical Code sets two limits and tells you which load to calculate with.

3%

Maximum in any one feeder or branch circuit.

5%

Maximum in total, from the supply side of the consumer’s service to the point of use.

80%

Of the breaker or fuse rating, used as the load when the connected load isn’t known.

The two limits work together. A feeder at 2% leaves 3% for the branch circuit. A feeder at 3% leaves only 2% for the branch circuit, even though 3% would be allowed on its own. When you check a branch circuit, look at the feeder that serves the panel too.

Diagram of the Canadian Electrical Code Rule 8-102 voltage drop budget from service to main panel, feeder, sub-panel and branch circuit: feeder 2% plus branch 3% passes at 5%, feeder 3% plus branch 3% fails at 6%
The 5% budget runs from the service to the load. No single feeder or branch circuit may use more than 3% of it.

Ontario’s Electrical Safety Authority explains how this is applied in dwellings in Bulletin 8-6-5. Three points from it are worth knowing:

  • The calculation uses the connected load if it is known, or 80% of the rating of the overcurrent device protecting the circuit.
  • In a dwelling unit, lighting and general-use branch circuits rated 20 A or less at 120 V can be checked against the maximum lengths in Table 68 instead. Appliance circuits, kitchen counter receptacles and heating and cooking circuits are excluded and still need the full calculation.
  • If the service and feeder conductors to a combination service panel are shorter than 20 m, they can be left out, and the branch circuits may then use up to 5%.

The code’s own lookup method is Table D3, which lists the distance for a 1% drop at 120 V and scales it for other voltages, percentages and conductor temperatures. This calculator works from conductor resistance instead, so it covers any voltage, length and size, and gives the same answer: set 12 AWG, 16 A, 120 V, a 1% limit and 60 °C, and Max distance returns the 6.1 m that Table D3 lists.

How far common circuits can run at 3%

BreakerCopper wireLoad (80%)120 V208 V240 V347 V
15 A14 AWG12 A14.6 m (48 ft)25.3 m (83 ft)29.2 m (96 ft)42.2 m (138 ft)
20 A12 AWG16 A17.4 m (57 ft)30.2 m (99 ft)34.8 m (114 ft)50.3 m (165 ft)
30 A10 AWG24 A18.4 m (61 ft)32.0 m (105 ft)36.9 m (121 ft)53.4 m (175 ft)
40 A8 AWG32 A22.0 m (72 ft)38.1 m (125 ft)44.0 m (144 ft)63.6 m (209 ft)
50 A6 AWG40 A28.0 m (92 ft)48.5 m (159 ft)56.0 m (184 ft)80.9 m (266 ft)
60 A6 AWG48 A23.3 m (77 ft)40.4 m (133 ft)46.6 m (153 ft)67.4 m (221 ft)

Maximum one-way length for a 3% drop on a single-phase circuit, copper at 75 °C, load at 80% of the breaker. 208 V is a two-wire circuit between two phases. Breaker and wire pairings are typical copper choices, not an ampacity check.

Canada and the US compared

Canada (CEC Rule 8-102)US (NEC)
StatusMandatory code ruleInformational notes, a recommendation in most cases
One feeder or branch circuit3% maximum3% recommended for branch circuits
Service or feeder to the load5% maximum5% recommended for feeder plus branch
Load to calculate withConnected load, or 80% of the breaker ratingLeft to the designer
Units on drawingsMetres, AWG and kcmil, mm² in tablesFeet, AWG and kcmil

The calculator works for both. Switch to feet and keep the 3% and 5% settings for a US job.

Voltage drop on 12 V and 24 V low-voltage runs

Low-voltage circuits are where voltage drop bites hardest. Losing 1 V on a 120 V circuit is 0.8%. Losing the same 1 V on a 12 V maglock circuit is 8.3%. Access control, camera and LED runs are also long and use thin wire, so a run that looks fine on paper can leave a lock buzzing or a strike that won’t release.

There is no single code percentage for these devices. The practical limit is the operating range on the device’s data sheet. Many locks, strikes and controllers are rated to work within about 10% of nominal, so the low-voltage presets use 10%. Check the cut sheet for the exact figure.

Maximum one-way distance at a 10% drop

12 V DC0.25 A0.5 A1 A2 A
22 AWG41.2 m (135 ft)20.6 m (68 ft)10.3 m (34 ft)5.1 m (17 ft)
20 AWG65.5 m (215 ft)32.7 m (107 ft)16.4 m (54 ft)8.2 m (27 ft)
18 AWG104 m (342 ft)52.1 m (171 ft)26.0 m (85 ft)13.0 m (43 ft)
16 AWG166 m (543 ft)82.8 m (272 ft)41.4 m (136 ft)20.7 m (68 ft)
14 AWG263 m (864 ft)132 m (432 ft)65.8 m (216 ft)32.9 m (108 ft)
12 AWG419 m (1374 ft)209 m (687 ft)105 m (343 ft)52.3 m (172 ft)
24 V DC0.25 A0.5 A1 A2 A
22 AWG82.4 m (270 ft)41.2 m (135 ft)20.6 m (68 ft)10.3 m (34 ft)
20 AWG131 m (430 ft)65.5 m (215 ft)32.7 m (107 ft)16.4 m (54 ft)
18 AWG208 m (683 ft)104 m (342 ft)52.1 m (171 ft)26.0 m (85 ft)
16 AWG331 m (1087 ft)166 m (543 ft)82.8 m (272 ft)41.4 m (136 ft)
14 AWG527 m (1728 ft)263 m (864 ft)132 m (432 ft)65.8 m (216 ft)
12 AWG837 m (2747 ft)419 m (1374 ft)209 m (687 ft)105 m (343 ft)

Copper at 40 °C, two-wire DC. Divide the distance by the number of devices sharing the same pair, or add their currents in the calculator.

A few habits keep low-voltage runs reliable:

  • Use 24 V where the device allows it. Half the current and twice the voltage cut the percentage drop to a quarter on the same wire.
  • Add up shared loads. Two maglocks on a double door draw twice the current on the same pair.
  • Use the right conductors. Composite access control cable usually has an 18 AWG pair for lock power. Don’t power a lock over the 22 AWG reader conductors.
  • Size camera runs for the heater. A 24 V AC outdoor camera can draw several times its daytime current when the heater runs in winter.
  • Put the supply closer. A power supply in the IDF or at the door beats a long run from the main closet.
  • Measure the supply. Check the actual output with a meter. Some battery-backed supplies sit slightly above nominal, which gives a little headroom.

For door hardware power and cabling, see our guide to commercial door hardware for access control and the access control wire gauge guide. PoE devices are different: the power runs over the Cat6 pairs and the switch budget matters too, so use the PoE power calculator for those.

How to reduce voltage drop

  1. Use a larger wire. Every three AWG sizes doubles the copper area and halves the resistance. 12 AWG to 10 AWG cuts the drop by about 37%.
  2. Raise the voltage. The same power at 240 V instead of 120 V draws half the current, and the percentage drop falls to a quarter. 347 V and 600 V lighting and equipment circuits exist for the same reason.
  3. Shorten the run. Drop is directly proportional to length. A subpanel or a local power supply near the loads can fix several circuits at once.
  4. Choose copper. Aluminum has about 1.65 times the resistance of copper of the same size.
  5. Run conductors in parallel. On large feeders, two sets of conductors per phase halve the resistance. Set this under Advanced.
  6. Split the load. Two circuits carrying half the current each have half the drop.

Wire resistance table

These are the resistance values the calculator uses at 75 °C. Multiply by 2 × current × one-way length for single-phase and DC, or by 1.732 × current × length for three-phase.

SizeArea (mm²)Copper Ω/kmCopper Ω/1000 ftAluminum Ω/kmAluminum Ω/1000 ft
22 AWG0.32665.7020.02
20 AWG0.51841.3212.59
18 AWG0.82325.997.920
16 AWG1.30916.344.981
14 AWG2.08110.283.133
12 AWG3.3096.4641.97010.643.244
10 AWG5.2614.0651.2396.6942.040
8 AWG8.3662.5570.77924.2101.283
6 AWG13.31.6080.49012.6480.8070
4 AWG21.21.0110.30821.6650.5075
3 AWG26.70.80190.24441.3210.4025
2 AWG33.60.63590.19381.0470.3192
1 AWG42.40.50430.15370.83050.2531
1/0 AWG53.50.39990.12190.65860.2007
2/0 AWG67.40.31720.09670.52230.1592
3/0 AWG85.00.25150.07670.41420.1262
4/0 AWG107.20.19950.06080.32850.1001
250 kcmil126.70.16880.05150.27800.0847
300 kcmil152.00.14070.04290.23170.0706
350 kcmil177.30.12060.03680.19860.0605
400 kcmil202.70.10550.03220.17380.0530
500 kcmil253.40.08440.02570.13900.0424
600 kcmil304.00.07030.02140.11580.0353
750 kcmil380.00.05630.01720.09270.0282
1000 kcmil506.70.04220.01290.06950.0212

DC resistance of one stranded conductor at 75 °C. Calculated from the conductor area and the standard resistivity of annealed copper (100% IACS) and 1350 aluminum (61% IACS). The values agree with NEC Chapter 9, Table 8 to within 0.5%. Aluminum building wire starts at 12 AWG.

Common voltage drop mistakes

  • Doubling the length. The formula already counts the return wire. Enter the one-way length.
  • Using the full breaker rating as the load. When the load is unknown, the CEC uses 80% of the breaker. Using 100% oversizes the wire.
  • Checking the branch circuit only. A branch circuit at 3% fails if the feeder ahead of it already used more than 2%.
  • Forgetting the temperature. Hot wire has more resistance. A loaded conductor at 75 °C has about 22% more resistance than at 20 °C.
  • Confusing voltage drop with ampacity. Passing the voltage drop check doesn’t mean the wire can carry the current. Check the amp to wire size chart as well.
  • Mixing up metric and AWG sizes. 2.5 mm² sits between 14 AWG (2.08 mm²) and 12 AWG (3.31 mm²). It isn’t a direct swap for either.

Voltage drop questions

What is the maximum voltage drop allowed in Canada?

Rule 8-102 of the Canadian Electrical Code allows a maximum of 3% in any one feeder or branch circuit, and 5% in total from the supply side of the consumer’s service to the point of use. The drop is calculated on the connected load if you know it, or on 80% of the breaker or fuse rating if you don’t.

How do I calculate voltage drop?

For DC and single-phase AC, voltage drop = 2 × current × one-way length × resistance per metre. For three-phase, replace the 2 with 1.732. Divide the result by the supply voltage and multiply by 100 to get the percentage. The calculator above does this and shows the full working under Show the math.

Is the length one way or the round trip?

Enter the one-way length, from the panel or power supply to the load along the route the cable takes. The formula already multiplies by 2 for the return wire on single-phase and DC circuits. Doubling the length yourself gives an answer twice as high as it should be.

What size wire do I need for 100 feet at 20 amps on 120 V?

With a real 20 A load, 100 feet one way at 120 V needs 8 AWG copper to stay under 3% (about 2.6%). 10 AWG gives about 4.1%. If 20 A is only the breaker size and the load is unknown, the CEC uses 16 A, and 10 AWG comes in at about 3.3%, which is still just over the limit.

How far can I run 12 gauge wire on a 20 amp circuit?

At 120 V with a 16 A load (80% of 20 A), 12 AWG copper reaches about 17 m (57 ft) one way before it passes 3%. On 240 V the same wire and load reach about 35 m (114 ft). These figures assume a loaded wire at 75 °C. A lightly loaded wire runs cooler and goes a little further.

How much voltage drop is acceptable on a 12 V or 24 V system?

Go by the voltage range on the device’s data sheet. Many 12 V and 24 V locks, strikes and controllers are rated to work within about 10% of nominal, which is why the low-voltage presets use 10%. LED strips show uneven brightness sooner, so the LED preset uses 5%. Battery and solar runs are usually held to 3% or less.

Why does three-phase use 1.732 instead of 2?

On a balanced three-phase circuit the currents in the three phases cancel at the neutral point, so there is no return current to double up. The line-to-line voltage drop works out to √3 (1.732) times the drop in one conductor, which is about 13% less than the single-phase factor of 2 for the same current.

Does aluminum wire have more voltage drop than copper?

Yes. Aluminum has about 1.65 times the resistance of copper of the same size. A rough rule is that aluminum needs to be two AWG sizes larger than copper for the same voltage drop. Switch the material in the calculator to see the exact size.

Does wire temperature change the voltage drop?

Yes. Copper resistance rises about 0.4% for every degree Celsius. A conductor at 75 °C has about 22% more resistance than the same conductor at 20 °C. The calculator uses 75 °C for building wire and 40 °C for low-voltage presets. You can change it under Advanced settings.

Does this match CEC Table D3?

Yes, within rounding. Table D3 lists 6.1 m for a 1% drop on 12 AWG copper at 16 A and 120 V. Set the calculator to 12 AWG, 16 A, 120 V, a 1% limit and 60 °C under Advanced settings, choose Max distance, and it returns 6.1 m.

Related tools and guides

Planning access control, cameras or new circuits in the GTA?

Cablify designs and installs structured cabling, access control and security cameras across Toronto and the GTA. Electrical work on our projects is carried out by an ECRA/ESA Licensed Electrical Contractor. See our electrical services.

Ask for a quote

This calculator gives estimates for planning. Results depend on the inputs and assumptions shown. It doesn’t replace a design by a qualified person or the requirements of the Canadian Electrical Code, the Ontario Electrical Safety Code and your inspection authority.

Service areasTorontoMississaugaBramptonVaughanMarkham & Richmond HillOakvilleMilton & HaltonBoltonAurora & NewmarketBarrieHamilton & BurlingtonGuelphKitchener-WaterlooLondonSt. Catharines & NiagaraMontrealVancouver

© 2026 Cablify. Commercial network cabling and fiber optic installation across Toronto and the GTA.

Call 1-647-846-1925Get a Free Quote